Measurement pages

Page

Displayed measurements

Description

Note

1

kWh+ TOT

Imported active energy (TOTAL)

 

2

kWh- TOT

Exported active energy (TOTAL)

Not available in PFA and SFA models

3

kW

Active power

 

4

V L-N

Voltage

 

5

A

Current

 

6

PF

Power factor

 

7

Hz

Frequency

 

8

THD V

Voltage THD

 

9

THD A

Current THD

 

10

kvarh+ TOT

Imported reactive energy (TOTAL)

Not available in SFA models

11

kvarh- TOT

Exported reactive energy (TOTAL)

Not available in SFA models

12

kvar

Reactive power

Not available in SFA models

13

kVAh

Apparent energy (TOTAL)

Not available in SFA models

14

kVA

Apparent power

Not available in SFA models

15

kW dmd

Demand active power

 

16

kW peak dmd

Peak demand active power

 

17

kWh T1

Imported active energy, tariff 1

Not available in SFA models

18

kWh T2

Imported active energy, tariff 2

Not available in SFA models

19

h (kWh+) TOT

Run hour meter (imported energy)

 

20

h (kWh-) TOT Run hour meter (exported energy)

Not available in PFA and SFA models

21

h (ON time) TOT Run hour meter (ON time) TOT

 

22

kWh+ PAR

Imported active energy (PARTIAL)

Not available in SFA models

23

h (kWh+) PAR

Run hour meter (imported energy, PARTIAL) PARTIAL

Not available in SFA models

24

kWh- PAR

Exported active energy (PARTIAL)

Not available in PFA and SFA models

25

h (kWh-) PAR

Run hour meter (exported energy, PARTIAL)

Not available in PFA and SFA models

SETTINGS menu

This menu allows to set the parameters.

Page title

Sub-menu

Description

Values

Default values

Note

Meas

-

Measurement mode

A (easy connection)

B (bidirectional)

A

Non MID only

DMD

-

DMD interval

1 min

5 min

10 min

15 min

20 min

30 min

60 min

15 min

 

inPut

-

Digital input

Tariff (tariff management)

Status (remote status)

P st (Start/stop partial meters)

P res (partial meter reset)

Status

 

RS485

Addr

Address

1 to 247

1

 

PArity

Parity

NO/EVEN

no

bAud

Baudrate

9.6 kbps

19.2 kbps

38.4 kbps

57.6 kbps

115.2 kbps

9.6 kbps

StoP bit

Stop bit

1 or 2

1

M bus

Pri Add

Primary address

0 to 250

0

 

bAud

Baudrate

0.3 kbps

2.4 kbps

9.6 kbps

2.4 kbps

Output

Fun

Function

Off

PuLSE (kWh+): pulse output

linked to kWh+

PuLSE (kWh-): pulse output

linked to kWh-

ALArM: linked to alarm status

PuLSE (kWh+)

 

durAt

Pulse duration

30 ms

100 m

30 ms

PuLSES

Pulse weight (pulses/kWh)

0.1/1/10/100/500/1000

1000

StAtuS

Output status

No (normally open)

Nc (normally closed)

No

ALARM

EnAbLE

Enable

ON/OFF

OFF

 

VAriAb

Monitored variable

kW

kVA

Kvar

PF

A

V

kW

 

SEt 1

Set point 1 (activation)

-1000.00 to 1000.00

0

 

Set 2

Set point 2 (deactivation)

-1000.00 to 1000.00

0

 

dELAY

Activation delay

0 to 1000 s

0

 

dISPL

LiGHt

backlight

ON (always on)

1 min

2 min

5 min

10 min

15 min

30 min

60 min

oFF: always off

ON

 

SC SAV

Screensaver

oFF

home: homepage

SLidE: slideshow

home

 

HOME

homepage

1 to 25

1

Only 1 in PFA or SFA models

Only 1 or 2 in PFB models

PAGES

Page filter

ALL

FiLtEr

ALL

 

PASS

Password enabling for the SETTINGS and RESET menu

0 (not protected) to 9999

0 (not protected)

 

bAcK ---

-

Exit

-

-

 

INFO menu

This menu allows to display the set parameters.

Page title

Description

Notes

YEAr

Production year

 

Sn

Serial number

Sliding digits

FW rEV

FW revision

 

MEAs

Measurement type

 

dMd

Demand calculation interval

 

Input

Digital input function

 

Addr

Address

 

bAud

Baudrate (kbps)

 

PArity

Parity

 

StoP b

Stop bit

 

PriAdd

M-Bus primary address

 

bAud

M-Bus baudrate

 

SECAdd

M-Bus secondary address

 

output

Digital output function

 

StAtuS

Current output status

 

durat

Pulse output duration

 

PuLSE

Output pulse weight

 

ALArM

Alarm enabling

 

VAr

Linked variable

 

SEt 1

Alarm activation set point

 

SEt 2

Alarm deactivation set point

 

dELAY

Alarm activation delay

 

LIGHt

Backlight timer

 

tEMP

Internal microcontroller temperature

Available only in PFA70 and PFB70 models. For further information refer to the communication protocol

CHECKSuM

Firmware checksum

 

RESET menu

This menu allows to reset the following settings:

Page

Page title

Description

1

PArtiAL

It resets the partial meters

2

DMD

It resets the dmd calculation

3

tAriFF

It restores the factory settings

4

total

It resets the total meters (only non MID)

5

FACtor

It resets the device to factory settings

6

Back---

Back to main menu

Communication Interface

Available setting parameters:

Parameter name

Description

Available on UI

Available on RS485

Available on Mbus

S1 Model M1 Model O1 Model only S1 Model only M1 model

Password

Password for accessing parameters via UI X X X X

 

DMD time

Time for DMD calculation (average on measures) X X X X

 

Alarm enable

Enable or disable the virtual alarms X X X X

 

Alarm link

Variable linked to the alarm X X X X

 

Alarm SET1

Alarm setpoint 1 X X X X

 

Alarm SET2

Alarm setpoint 2

X X X X

 

Alarm Delay

Alarm delay

X X X X

 

Measure mode

Type of measurement

X* X* X* X*

 

Digital input selection

Function of the digital input

X X X X

 

Page Filter

Filter on real-time pages

X* X* X* X*

 

Screen saver

Indicates what happens after 300s of inactivity

X* X* X* X*

 

Home page

Page on startup or when the UP button is pressed for 2s

X** X** X** X**

 

Backlight

Backlight time

X X X X

 

Screen saver time

Page rotation time when using screensaver

 

 

 

X***

 

Tariff management

Configuration to enable the tariff management via serial

 

 

 

X

 

Quick setup

Restores the initial quick setup menu

 

 

 

X

 

Startup current

Set the start-up current only for hour counters

 

 

 

X

 

Current direction

Direction of the input current

 

 

 

X***

 

Tariff selection

Tariff selection

 

 

 

X

X

Pages cfg

Dedicated register for each Real time page to configure the visibility

 

 

 

X*

 

Device name

Registers to set a device name

 

 

 

X

 

RS485 Address

RS485 address

X

 

 

X

 

RS485 Baud

RS485 baudrate

X

 

 

X

 

RS485 Parity

RS485 parity

X

 

 

X

 

RS485 Stop

RS485 Stop bits

X

 

 

X

 

Delay on reply

Minimum time before answering

 

 

 

X

 

MBUS Address

MBUS primary address

 

X

 

  X

MBUS Baud

MBUS baudrate

 

X

 

  X

OUT Config.

Output configuration

 

 

X  

 

OUT Type

Output NO or NC

 

 

X  

 

Pulse duration

Pulse duration

 

 

X  

 

Pulse weight

Pulse weight

 

 

X  

 

* = Read-Only on MID models

** = Home page can be set only to 1 in PFA and SFA and between 1 and 2 on PFB

*** = Not available on MID models