Troubleshooting

Note: in case of other malfunctions or of any failure, please contact the CARLO GAVAZZI branch or the distributor for your country

Problem

Cause Possible solution

The ‘EEEE’ indication is displayed instead of a measurement

The analyser is not used within the prescribed measuring range; as a consequence, the measurement exceeds the maximum permitted value or is the result of a calculation with at least one measurement in error. Uninstall the analyser

The analyser has just been switched on and the interval defined for the calculation of the average power values (default: 15 min) has not expired yet.

Wait. If you wish to change the interval, access the Dmd page of the Settings menu

The displayed values are not the expected ones

Electrical connections are incorrect

Verify the connections

Exported energy meters (kWh-) don’t increase

Measurement mode is set to A (default setting)

Set Measurement mode from A to B via keypad or UCS

Alarms

Problem

Cause Possible solution

An alarm is triggered, but the measurement has not exceeded the threshold value

The value with which the alarm variable is calculated is in error

Check the connections

The alarm is not activated and deactivated as expected

The alarm settings are incorrect

Check the set parameters

Communication problems

Problem

Cause Possible solution

No communication can be established with the analyser

Communication settings are incorrect

Check the set parameters

Communication connections are incorrect

Verify the connections

The settings of the communication device (third-party PLC or software) are incorrect

Check the communication with the UCS software

Display problem

Problem

Cause Possible solution

You cannot display all measurement pages

The page filter is enabled

Disable the filter, see Page filter